Programming Overview
151295 6-17
System
Options
(cont.)
System Event
Outputs
Trouble Events
System Trouble
Select Group
None selected
Section 7.6.3.1
Select Cadence
Alarm Silence Select Group
None selected
Select Cadence
Trbl Silence
Select Group
None selected
Select Cadence
User Selected
Group Tr
Select Group
SBUS Com
SBUS Pwr
SLC Loop
AC Loss
Battery
Gnd Flt
Select
Cadence
Phone Ln
Account
Printer
Aux Pwr
Sys Sw
Sys Alarm Cadence
Fire Drill
Select Cadence Constant
Section 7.6.3.2
System Aux1
System Aux2
Misc. Options 1
Water Flow Delay
0 - 90 Seconds *30 sec Water Flow delay is the number of
sec. before water flow alarm is
generated. Section 7.6.4.1
Low AC Delay
0 - 30 hours *3 hrs Low AC Report
Delay.
Section 7.6.4.2
DST
Y (Enabled)
*Enabled
Automatic Daylight Saving Time
enable or disable. Section 7.6.4.3
and 7.6.6.2. See also DST settings
in Misc. Option 3, below.
N (Disabled)
CLK
AM/PM
*AM/PM
System Clock Format (AM/PM or
military). Sec. 7.6.4.4
MIL
AC Freq:
NA Section 7.6.4.5
60 Hz
Neither
Misc. Options 2
SYNC Strbs w/ Sil
Y (Enabled)
*Disabled
Section 7.6.5.1
N (Disabled)
Auto Display Oldest
Y (Enabled)
*Disabled
Section 7.6.5.2
N (Disabled)
Report By
Zone
*Zone
Section 7.6.5.3
Point
Misc. Options 3
Alarm Verification
time
Enter time from 1 to
250 seconds
*60 Seconds
Section 7.6.6
Note: For UL installations no less
than 60 seconds.
DST Start
Select week: 1st,
2nd, 3rd, 4th or Last
Select month
Section 7.6.4.3 and 7.6.6.2. See
also DST settings in Misc.
Options 1, above.
DST End
Edit Banner
Internal Message Section 7.6.7
Custom Message
Edit Line 1
Edit Line 2
Menu Options/Defaults Comments