3-2 151295
3.3 Electrical Specifications
Table 3-1 list the terminal block on the 5700 as well as a description of the each individual
terminal and their respective electrical rating. For location of the terminals refer to Figure 3-2.
See also Section 4 for installation.
* Regulated NAC application. When programmed for releasing, NAC are Special Application.
Table 3-1: Terminal Descriptions
Terminal No.
Label
Description
Rating
Group Individual Voltage Current
Terminal Block 1
RELAY 1
NO Normally open relay contact
27.4 VDC 2.5 A, resistiveCOM Common terminal
NC Normally closed relay contact
RELAY 2
NO Normally open relay contact
27.4 VDC 2.5 A, resistiveCOM Common terminal
NC Normally closed relay contact
Terminal Block 2
TELCO 1
RING Phone Line 1 Telco Ring
TIP Phone Line 1 Telco Tip
PHONE 1
RING Phone Line 1 Phone Ring
TIP Phone Line 1 Phone Tip
TELCO 2
RING Phone Line 2 Telco Ring
TIP Phone Line 2 Telco Tip
PHONE 2
RING Phone Line 2 Phone Ring
TIP Phone Line 2 Phone Tip
TROUBLE
NO Normally open relay contact
27.4 VDC 2.5 A, resistiveCOM Common terminal
NC Normally closed relay contact
SLC IN
Used for Class A installations 32 VDC 100 mA
+
SLC OUT
SLC terminals 32 VDC 100 mA
+
SLC PROG
Used for programming SLC
Detectors
32 VDC 100 mA
+
SBUS
SBUS Power 27.4 VDC 0.5 A
+
A
SBUS Communication 5 VDC 100 mA
B
NAC1*
Notification Appliance
Circuit/Auxiliary power
27.4 VDC
2.5 Amp NAC or Aux
power
+
NAC2*
Notification Appliance
Circuit/Auxiliary power
27.4 VDC
2.5 Amp NAC or Aux
power
+